Quadra-Fire 7100FP-GD-B Indoor Fireplace User Manual


 
September 7, 2007
433-1390D
Page 25
7100FP EPA Woodburning Fireplace
R
G. Install the Attic Insulation Shield
An insulation shield must be installed when there is a pos-
sibility of insulation coming into contact with the factory built
chimney system.
Bend the tabs at the top of the attic insulation shield inward.
This will help keep the chimney section centered in the
shield.
Position the shield over the vertical chimney section where
it penetrates a ceiling restop.
Slide the shield down until it rests on the ceiling restop.
The ceiling restop will support the insulation shield. See
Figures 25.1 and 25.2.
H. Double-check the Chimney Assembly
Continue assembling the chimney sections up through the
ceiling restops as needed. While doing so, be aware of the
height and unsupported chimney length limitations given un-
der Section 5.A. Chimney Requirements.
Check each section by pulling up slightly from the top to en-
sure proper engagement before installing the succeeding
sections. If they have been connected correctly, they will not
disengage when tested.
I. Secure the Chimney
When offsets and returns are joined to straight pipe sections,
they must be locked into position with the screws provided*
(outer only), using the predrilled holes. To prevent gravity
from pulling the chimney sections apart, the returns and the
chimney stabilizers have hanger straps for securing these
parts to joists or rafters. See Figure 25.3.
* Use #6 or #8 sheet metal screw, or larger, no longer than
1/2 in. (13mm).
Attic Insulation
Shield
Chimne
y
Insulation
Ceiling Firestop
Tabs
24 in.
(610mm)
10-1/2 in.
(267mm)
14-1/2 in. (368mm)
2 in. (51mm)
Figure 25.1 Install Attic Insulation Shield Above the Ceiling
24 in.
(610 mm)
Attic
Insulation
Shield
Chimne
y
Insulation
10-1/2 in.
(267 mm)
14-1/2 in. (368 mm)
Ceiling Firestop
Tabs
2 in. (51mm)
Figure 25.2 Install Attic Insulation Shield Below the Ceiling
Ceiling
Firestop
Straps
Optional
A
dditional
Support
Joint
Band
(Optional)
Figure 25.3 Secure the Chimney
Fire Risk
Secure offsets with screws (not to exceed
1/2 in. / 13mm in length).
WARNING
Secure returns with strapping.
Straight chimney sections may be secured with screws
(not to exceed 1/2 in./13 mm in length) at the joints.
Keep chimney sections from separating or twisting.
Fire Risk
DO NOT pack insulation or other combustibles:
between ceiling restops; between chimney
and attic insulation shield.
ALWAYS maintain speci ed clearances around
chimney and ceiling restop systems.
WARNING
• Install ceiling restops as speci ed.
Failure to keep insulation or other material away from chimney
pipe may cause re
.