Chapter 7: Programming
RECOGNITION
The recognition time is the length of time that an alarm condition must exist continuously
before ISACC will consider it a valid alarm and initiate a response. This keyword allows you
to program the recognition time for each input.
To display the currently programmed recognition times, type show recognition after an
ISACC prompt. You may also display the recognition time for a specific input by typing show
recognition followed by the input number.
ISACC>show recognition
INPUT RECOGNITION TIME
IN01 = "LOW WELL FLOAT " = 000 Min 003 Sec
IN02 = "HI SUMP FLOAT " = 000 Min 003 Sec
IN03 = "Input #3 " = 000 Min 003 Sec
IN04 = "FLOW RATE (GPM) " = 000 Min 003 Sec
IN05 = "WELL LEVEL (FT) " = 000 Min 003 Sec
IN06 = "RESET " = 000 Min 003 Sec
IN07 = "Input #7 " = 000 Min 003 Sec
IN08 = "VOLTAGE " = 000 Min 003 Sec
IN09 = "Input #9 " = 000 Min 003 Sec
IN10 = "Input #10 " = 000 Min 003 Sec
IN11 = "Input #11 " = 000 Min 003 Sec
IN12 = "Input #12 " = 000 Min 003 Sec
IN13 = "Input #13 " = 000 Min 003 Sec
IN14 = "Input #14 " = 000 Min 003 Sec
IN15 = "Input #15 " = 000 Min 003 Sec
IN16 = "Input #16 " = 000 Min 003 Sec
To program the recognition times, type set recognition after an ISACC prompt. Enter a new
value for the minutes and press ENTER. Enter a new value for the seconds and press EN-
TER to go to the next parameter. You may also program the recognition time of a specific
input by typing set recognition followed by the input number.
ISACC>set recognition
INPUT RECOGNITION TIME
IN01 = "LOW WELL FLOAT " = 000 Min 003 Sec New minutes > New seconds >001
IN02 = "HI SUMP FLOAT " = 000 Min 003 Sec New minutes > New seconds >001
IN03 = "Input #3 " = 000 Min 003 Sec New minutes > New seconds >001
IN04 = "FLOW RATE (GPM) " = 000 Min 003 Sec New minutes >001 New seconds >030
IN05 = "WELL LEVEL (FT) " = 000 Min 003 Sec New minutes >005 New seconds >000
IN06 = "RESET " = 000 Min 003 Sec New minutes > New seconds >
IN07 = "Input #7 " = 000 Min 003 Sec New minutes >010 New seconds >000
IN08 = "VOLTAGE " = 000 Min 003 Sec New minutes >001 New seconds >030
IN09 = "Input #9 " = 000 Min 003 Sec New minutes > New seconds >
IN10 = "Input #10 " = 000 Min 003 Sec New minutes > New seconds >
IN11 = "Input #11 " = 000 Min 003 Sec New minutes > New seconds >
IN12 = "Input #12 " = 000 Min 003 Sec New minutes > New seconds >
IN13 = "Input #13 " = 000 Min 003 Sec New minutes > New seconds >
IN14 = "Input #14 " = 000 Min 003 Sec New minutes > New seconds >
IN15 = "Input #15 " = 000 Min 003 Sec New minutes > New seconds >
IN16 = "Input #16 " = 000 Min 003 Sec New minutes > New seconds >