Pelco ALM2064 Home Security System User Manual


 
C1517M-A (11/02) 13
Figure 13. SW1 & SW2 Functions
1-32 33-64
Off Off Off Off
Off On Off On
On Off On Off
On On On On
Norm. Open
(Unsupervised)
Norm. Closed
(Unsupervised)
Supervised
*Default to
Norm. Open
SERIAL PORT 1
BAUD RATE
1200: OFF, OFF, OFF
2400: ON, OFF, OFF
4800: OFF, ON , OFF
9600: ON, ON, OFF
19200: OFF, OFF, ON
38400: ON, OFF, ON
57600: OFF, ON, ON
115200: ON, ON, ON
BEGIN ALARM RANGE
1-64: OFF, OFF, OFF
65-128: ON, OFF, OFF
129-192: OFF, ON, OFF
193-256: ON, ON, OFF
257-320: OFF, OFF, ON
321-384: ON, OFF, ON
385-448: OFF, ON, ON
449: ON, ON, ON
ALARM GROUP 1-32
N.O. UNSUP: OFF, OFF
N.C. UNSUP: OFF, ON
SUP: ON, OFF
DEFAULT N.O.: ON, ON
ALARM GROUP 33-64
N.O. UNSUP: OFF, OFF
N.C. UNSUP: OFF, ON
SUP: ON, OFF
DEFAULT N.O.: ON, ON
DEFAULT SETTINGS: LOCAL DEVICE ADDRESS 1, DIP SWITCH 9 OFF, DIP SWITCH 10 ON
NOTE: REFER TO APPENDIX A FOR SETTING EACH DEVICE ADDRESS (1-253)
N.O. = NORMALLY OPEN
N.C. = NORMALLY CLOSED
SUP = SUPERVISED
UNSUP = UNSUPERVISED
DEFAULT SETTINGS: BAUD 19200, ALARM RANGE 1-64, ALARM GROUPS N.O.
DIAGNOSTICS: OFF
LOCAL DEVICE ADDRESS
ON
1
2
3
4
5
6
7
8
9
10
NOT USED:
OFF
ON
1
2
3
4
5
6
7
8
9
10
00718
Table B. Switch 2
Address SW2 – Address
1 Off Off Off Off Off Off Off Off Off Off
2 On Off Off Off Off Off Off Off Off Off
3 Off On Off Off Off Off Off Off Off Off
4 On On Off Off Off Off Off Off Off Off
5 Off Off On Off Off Off Off Off Off Off
6 On Off On Off Off Off Off Off Off Off
7 Off On On Off Off Off Off Off Off Off
8 On On On Off Off Off Off Off Off Off
9 Off Off Off On Off Off Off Off Off Off
10 On Off Off On Off Off Off Off Off Off
11 Off On Off On Off Off Off Off Off Off
12 On On Off On Off Off Off Off Off Off
13 Off Off On On Off Off Off Off Off Off
14 On Off On On Off Off Off Off Off Off
15 Off On On On Off Off Off Off Off Off
16 On On On On Off Off Off Off Off Off
DIP Switch 1 2 3 4 5 6 7 8 9 10
Table A. Switch 1
SW1 – Communications/Alarm Type Selection
Baud Alarm Range Alarm Mode
1200 Off Off Off 1-64 Off Off Off
2400 On Off Off 65-128 On Off Off
4800 Off On Off 129-192 Off On Off
9600 On On Off 193-256 On On Off
19200 Off Off On 257-320 Off Off On
38400 On Off On 321-384 On Off On
57600 Off On On 385-448 Off On On
115200 On On On 449 On On On
DIP Switch 1 2 3 4 5 6 7 8 9 10
*The alarm modes default to normally open when DIP switches 7-10 are set to an invalid condition (all On).