9.4. Airflow Direction Control
Vertical louver is controlled with Vertical Airflow Direction button on remote controller and by operation conditions, as shown in the
table below.
9.4.1. Vertical Airflow Louver Angle
Cooling and Dry Operations
Airflow Direction Auto Airflow Direction Setting
Manual Operation Vertical Auto Operation Powerful-ON
It swings when airflow direction is set with
remote controller.
It does not swing while indoor fan is
stopped. (It is fixed at the upper limit.).
The louver is fixed at five-level setting
position when the airflow direction is set with
remote controller.
Heating Operation
Airflow Direction Auto Airflow Direction Setting
Fixed by Heat Exchanger Temperature Powerful Operation Remote Control
When Heat Exchanger Temperature is less
than 33°C
When Heat Exchanger Temperature is
between 33°C (, incl.) and 127°C
When Heat Exchanger Temperature is less
than 33°C
When Heat Exchanger Temperature is
between 33°C (, incl.) and 127°C
The louver is fixed at five-level setting
position when the airflow direction is set with
remote controller.
Airflow Direction Auto Airflow Direction Setting
Odour Removal Control
The vertical louver is fully opened and move to the setting position when the unit is turned on with the remote controller.
The vertical louver remains open position when the unit is turned off during operation.
The horizontal louver is manually operated.
23
CS-TE9DKE CU-TE9DKE / CS-TE12DKE CU-TE12DKE