Panasonic CU-E21CKE Air Conditioner User Manual


 
Error Codes Table
Diagnosis
display
Abnormality / Protection control Abnormality
Judgement
Emergency
operation
Primary location to verify
H11 Indoor / outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
Internal / external cable connections
Indoor / Outdoor PCB
H14 Indoor intake air temperature sensor
abnormality
Continue for 5 sec.
Intake air temperature sensor
(defective or disconnected)
H15 Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
Compressor temperature sensor
(defective or disconnected)
H16 Outdoor Current Transformer open
circuit
Outdoor PCB
IPM (Power transistor) module
H19 Indoor fan motor merchanism lock
Indoor PCB
Fan motor
H23 Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec. O
(Cooling only)
Heat exchanger temperature sensor
(defective or disconnected)
H26 Ion abnormality
Indoor PCB
Ionizer
H27 Outdoor air temperature sensor
abnormality
Continue for 5 sec. O
Outdoor temperature sensor
(defective or disconnected)
H28 Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec. O
Outdoor heat exchanger
temperature sensor (defective or
disconnected)
H30 Discharge temperature sensor
abnormality
Continue for 5 sec.
Discharge temperature sensor
H33 Indoor/Outdoor wrong connection
Indoor/Outdoor supply voltage
H97 Outdoor Fan Motor lock abnormality
Outdoor PCB
Outdoor Fan Motor
H98 Indoor high pressure protection
Air filter dirty
Air circulation short circuit
H99 Indoor heat exchanger anti-freezing
protection
Insufficient refrigerant
Air filter dirty
F11 Cooling / Heating cycle changeover
abnormality
4 times occurance
within 30 minutes
4-way valve
V-coil
F90 PFC control 4 times occurance
within 10 minutes
Voltage at PFC
F91 Refrigeration cycle abnormality 7 times occurance
continuously
No refrigerant
(3-way valve is closed)
F93 Outdoor compressor abnormal revolution 4 times occurance
within 20 minutes
Outdoor compressor
F95 Cool high pressure protection 4 times occurance
within 20 minutes
Outdoor refrigerant circuit
F96 IPM (power transistor) overheating
protection
Excess refrigerant
Improper heat radiation
IPM (Power transistor)
F97 Outdoor compressor overheating
protection
4 times occurance
within 20 minutes
Insufficient refrigerant
Compressor
F98 Total running current protection 3 times occurance
within 20 minutes
Excess refrigerant
Improper heat radiation
F99 Outdoor Direct Current (DC) peak
detection
7 times occurance
continuously
Outdoor PCB
IPM (Power transistor)
Compressor
Note:
O - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until beep sound heard
following by pressing the RESET button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one beep to four beep sounds.
75