Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2
and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on
the above operation mode chart, every 30 minutes.
Remote Control Setting Temperature (°C) T1 T2 T3
16 ~ 18 +10 +8 -5
19 ~ 22 +8 +7 -7
23 ~ 26 +7 +6 -7
27 ~ 30 +6 +5 -8
There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice
verse.
Operation Mode change from Temperature shifts (°C)
Cooling/Soft Dry
→
Heating -2
Heating
→
Cooling/Soft Dry +2
Example of operation mode chart adjustment:
From the above table, if remote control setting temperature = 25,
T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on
indoor intake air temperature and outdoor air temperature at the time when the judgment is made.
8.1.7. Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
•
Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)
[Cooling, Dry, Fan]
Remote Control — O O O O O — — —
Tab (rpm) SHI Hi Me+ Me Me- Lo Lo- SLo SSLo
E18CK 1530 1440 1360 1290 1220 1150 850 760 630
E21CK 1610 1520 1420 1330 1240 1150 890 800 630
[Heating]
Remote Control — O O O O O — — —
Tab (rpm) SSHI SHi Me+ Me Me- Lo Lo- SLo SSLo
E18CK 1590 1560 1480 1410 1340 1270 850 400 300
E21CK 1640 1610 1520 1440 1350 1270 890 400 300