Combustible Wall Chimney Connector Pass-Throughs.
Method A. 12” (304.8 mm) Clearance to Combustible Wall
Member: Using a minimum thickness 3.5” (89 mm) brick and
a 5/8” (15.9 mm) minimum wall thickness clay liner, construct
a wall pass-through. The clay liner must conform to ASTM
C315 (Standard Specification for Clay Fire Linings) or its
equivalent. Keep a minimum of 12” (304.8 mm) of brick
masonry between the clay liner and wall combustibles. The
clay liner shall run from the brick masonry outer surface to
the inner surface of the chimney flue liner but not past the
inner surface. Firmly grout or cement the clay liner in place
to the chimney flue liner.
Method B. 9” (228.6 mm) Clearance to Combustible Wall
Member: Using a 6” (152.4 mm) inside diameter, listed factory-
built Solid-Pak chimney section with insulation of 1” (25.4 mm)
or more, build a wall pass-through with a minimum 9” (228.6
mm) air space between the outer wall of the chimney length
and wall combustibles. Use sheet metal supports fastened
securely to wall surfaces on all sides, to maintain the 9” (228.6
mm) air space. When fastening supports to chimney length,
do not penetrate the chimney liner (the inside wall of the Solid-
Pak chimney). The inner end of the Solid-Pak chimney
section shall be flush with the inside of the masonry chimney
flue, and sealed with a non-water soluble refractory cement.
Use this cement to also seal to the brick masonry penetration.
Method C. 6” (152.4 mm) Clearance to Combustible Wall
Member: Starting with a minimum 24 gage (.024” [.61 mm])
6” (152.4 mm) metal chimney connector, and a minimum 24
gage ventilated wall thimble which has two air channels of 1”
(25.4 mm) each, construct a wall pass-through. There shall
be a minimum 6” (152.4) mm separation area containing
fiberglass insulation, from the outer surface of the wall
thimble to wall combustibles. Support the wall thimble, and
cover its opening with a 24-gage minimum sheet metal
support. Maintain the 6” (152.4 mm) space. There should
also be a support sized to fit and hold the metal chimney
connector. See that the supports are fastened securely to
wall surfaces on all sides. Make sure fasteners used to
secure the metal chimney connector do not penetrate
chimney flue liner.
Method D. 2” (50.8 mm) Clearance to Combustible Wall
Member: Start with a solid-pak listed factory built chimney
section at least 12” (304 mm) long, with insulation of 1” (25.4
mm) or more, and an inside diameter of 8” (2 inches [51 mm]
larger than the 6” [152.4 mm] chimney connector). Use this
as a pass-through for a minimum 24-gage single wall steel
chimney connector. Keep solid-pak section concentric with
and spaced 1” (25.4 mm) off the chimney connector by way
of sheet metal support plates at both ends of chimney
section. Cover opening with and support chimney section on
both sides with 24 gage minimum sheet metal supports. See
that the supports are fastened securely to wall surfaces on all
sides. Make sure fasteners used to secure chimney flue liner.