11
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams.
It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case designed
to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation. Drain connections 2
- 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40
Recirculation mode, Recirculation mode (each mode has 5 speeds). Control
pad can be removed from HRV and remotely mounted.
Weight 87 lbs. (39.5 kg) Shipping Weight 89 lbs. (40.5 kg)
TOP VIEW
SIDE VIEW
25 1/2 "
(
648 mm)
26 1/2"
(673 mm)
22 1/2"
(572 mm)
FRONT VIEW
ALL DUCT CONNECTIONS
ARE 6" (150 mm)
18"
(457 mm)
7 1/2"
(191 mm)
SUPPLY OF
FRESH AIR
FRESH AIR
SUPPLY
TO BUILDING
STALE AIR
RETURN FROM
BUILDING
STALE AIR
EXHAUST
DRAIN
CONNECTION
CONTROLS
*Service Clearance
25" (635 mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)
99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5
year replacement parts warranty.
TI-100-NE
0107
Model MAXTOP
Allunits conformto
CSAand ULstandards.
DIMENSIONS MAXTOP
inches (mm
)
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#:_________________________________________
Submitted by: ____________________________________
*SensibleEfficiency –thermal **LatentEfficiency –moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance (HVI certified)
Netsupply airflow incfm (L/s)against externalstatic pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 196 (93)
@ 0.2" (50 Pa) 188 (89)
@ 0.3" (75 Pa) 178 (84)
@ 0.4" (100 Pa) 165 (78)
@ 0.5" (125 Pa) 149 (70)
@ 0.6" (150 Pa) 131 (62)
@ 0.7" (175 Pa) 109 (51)
@ 0.8" (200 Pa) 79 (37)
@ 0.9" (225 Pa) 48 (23)
Max. Temperature Recovery 83%
Sensible Effectiveness
@ 65 cfm (31 L/s) 32°F (0°C) 80%
*Sensible Efficiency
@ 65 cfm (31 L/s) 32°F (0°C) 69%
*Sensible Efficiency
@ 67 cfm (31 L/s) -13°F (-25°C) 70%
VAC @ 60HZ 120
WATTS / Low speed. 74
WATTS / High speed 164
Amp rating 1.4
1
2
3
4
5
20
40
60
80
100
120
140
160
180
200
220
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Static Pressure (in w.g.)
Air Flow (cfm)
5 - High Speed
*4 - Medium High Speed
*3 - Medium Speed
*2 - Medium Low Speed
*1 - Low speed
* Manufacturers Data