17
Status
LED
Status LED
Description
Status LED Troubleshooting Information
Green
“POWER”
Module has
power
Supply voltage is present at module terminals
Red “TRIP”
Thermostat
demand signal
Y is present, but
compressor is not
running
• Compressor protector is open
• Check for high head pressure
• Check compressor supply voltage
• Outdoor unit power disconnect is open
• Compressor circuit breaker or fuse(s) is open
• Broken wire or connector is not making contact
• Low pressure switch open if present in system
• Compressor contactor has failed open
Yellow “ALERT”
Flash Code 1
Long Run Time
Compressor is
running extremely
long run cycles
• Low refrigerant charge
• Evaporator blower is not running
— Check blower relay coil and contacts
— Check blower motor capacitor
— Check blower motor for failure or blockage
— Check evaporator blower wiring and connectors
— Check indoor blower control board
— Check thermostat wiring for open circuit
• Evaporator coil is frozen
— Check for low suction pressure
— Check for excessively low thermostat setting
— Check evaporator airfl ow (coil blockages or return airfi lter)
— Check ductwork or registers for blockage
• Faulty metering device
— Check TXV bulb installation (size, location and contact)
— Check if TXV/fi xed orifi ce is stuck closed or defective
• Condenser coil is dirty
• Liquid line restriction (fi lter drier blocked if present in system)
• Thermostat is malfunctioning
— Solenoid plug not connected
— Y2 not wired at Comfort Alert
— Check thermostat sub-base or wiring for short circuit
— Check thermostat installation (location, level)
• Comfort Alert failure
Yellow “ALERT”
Flash Code 2
System Pressure
Tr ip
• High head pressure
— Check high pressure switch if present in system
— Check if system is overcharged with refrigerant
— Check for non-condensable in system
Discharge or
suction
• Condenser coil poor air circulation (dirty, blocked, damaged)
pressure out of
limits
• Condenser fan is not running
— Check fan capacitor
— Check fan wiring and connectors
— Check fan motor for failure or blockage
compressor
overloaded
• Return air duct has substantial leakage
• If low pressure switch present in system, check Flash Code
1 information
TROUBLESHOOTING
Table 4. LED Diagnostics