Napoleon Fireplaces NZ25 Indoor Fireplace User Manual


 
WS-415-71 / 09.07.00
8
FIGURE 10 - 4 ELBOWSFIGURE 9 - 2 ELBOWSFIGURE 8 - STRAIGHT UP
No Off-Set. Minimum overall chim-
ney height is 15 feet.
Single off-set with two 15°, 30° or
45° elbows. Minimum overall
chimney height is 15 feet.
Double off-set with four 15°, 30° or
45° elbows. Minimum overall chim-
ney height is 15 feet.
CHIMNEY INSTALLATION
This fireplace was tested to CAN/ULC S610-M87 Zero Clearance Fireplace Safety Test Standard. In accordance with this
standard, the unit may be connected to any accepted chimney listed to ULC S-629. The following 7" factory-built chimney
systems may be used:
OLIVER MACLEOD HT 6103(
FORMERLY HT3103) 4 - 45
O
4 - 30
O
SECURITY ASHT 4 - 45
O
4 - 30
O
ICC EXCEL 2100-2 4 - 45
O
4 - 30
O
ENERGY VENT HT5103 4 - 45
O
4 - 30
O
GSW FC 2 - 45
O
& 2-15
O
4 - 30
O
SELKIRK METALBESTOS SSPLUS 2 - 45
O
2 - 30
O
LISTED TO
ULC S610-M87
::
::
:
(45
o
MAX.)
MAXIMUM # OF OFFSETSMODEL #
MANUFACTURER
(30
o
MAX.)
Installation of all types of factory-built chimney systems is to be in accordance with the chimney manufacturers installa-
tion instructions. An appropriate chimney manufacturers anchor base plate is required in order to initiate the twist lock
mechanism. Air cooled chimney systems are not recommended in colder climates.