FIREBOX FRAMING
Firebox framing can be built before or after the appliance
is set in place. Construct firebox framing following Figure
2 and the chart below for your specific installation require-
ments. See Figure 3 on page 8 for firebox dimensions. The
framing headers may rest on the top of the firebox standoffs.
Do not bring headers below top of standoffs. Please note:
When planning your framing and installation, keep in mind that your gas line will come in on the right side of the box (as
you are facing it) and your electricity will come in on the left side.
The firebox may be installed directly on a combustible floor
or raised on a platform of an appropriate height. When the
firebox is installed directly on carpeting, tile, or other com-
bustible material, other than wood flooring, the firebox shall
be installed on a metal or wood panel extending the full width
and depth of the enclosure.
FIREPLACE FRAMING
Do not ll spaces around rebox with
insulation or other materials. This
could cause a re.
WARNING
Figure 2 - Framing Dimensions
KHLDV400 KHLDV500
A 45 5/16" 49 5/16"
B 44 3/4" 44 3/4"
C 28 1/8" 32 1/8"
D 14 1/16" 16 1/16"
E 75 7/8" 79 7/8"
F 37 15/16" 39 15/16"
G 23 7/8" 23 7/8"
H 53 5/8" 56 7/16"
Unit framing is to be rectangular front
to back. Failure to do so will cause re
and damage to property.
WARNING