Monessen Hearth HBDV400 Indoor Fireplace User Manual


 
26 54D5031
FLEX VENT INSTALLATION
Flex vent pipe spacers: Refer to manufacturer’s
speci cations for correct positioning of the spacer springs to
maintain proper distance between inside and outside pipe.
NOTE
UL1777
Flex vent
Securing screws
(3 places
equidistant just
above gear
clamp)
Gear clamps
DVFA/8
inner adapter
outer adapter
Appliance starting
collar
1¾ in. exible pipe
and adapter outer
collar overlap
UL1777
Flex vent
5" radius
Figure 1 —
Typical appliance connection
Figure 2 —
Minimum radius for ex vent section
1. Flexible UL1777 listed venting may be used in any venting
application where rigid direct vent components can be used.
All restrictions, clearances and allowances that pertain to
the rigid piping apply to the exible venting. Flex kits may
not be modi ed. Flex kits may be added to the end of a vent
run made of rigid vent sections using pipe manufacturer’s
approved ex to pipe adapters. This may occur only if doing
so does not violate any of the venting length, height,
routing, horizontal to vertical ratio requirements or
clearance considerations detailed in this manual.
2. The ex adapter starter kit (DVFA/8) is used to attach ex
venting to the appliance starting collar. It includes 4" inner
and 7" outer adapter rings (refer to Figure 1).
The inner and outer adaptor rings are required to start
all ex runs.
Never install damaged or torn exible venting.
Over tightening clamps may rip, tear, or otherwise
damage exible venting.
The adaptor kit does not include individual pipe
sections which may be purchased separately. (UL1777
listed type ex venting only.)
3. Start the exible vent as follows—
A. Installing the inner ex adaptor and pipe (see Figure 1).
1. Insert the long side of the 4" inner ring inte exhaust
pipe, gently tap to seat into place, and secure with
screws.
2. Slide the small gear clamp over the inner exible vent pipe, and push out of the way.
3. Pull and extend the inner exible vent.
4. Slide the inner vent onto the adapter collar, for a minimum 1¾" overlap.
5. Locate the clamp at approximately ¾" from the ex end and tighten.
6. Secure the clamped inner section with three self tapping screws, drilled equidistance, just above the clamp
perimeter.
B. Installing the outer ex pipe (refer to Figure 1).
1. Firmly insert the outer adapter ring into the outer appliance starting collar and secure with screws.
2. Slide the large gear clamp over the outer exible vent pipe, and push out of the way.
3. Pull and extend the outer exible vent.
4. Slide the outer vent onto the appliance collar outer adapter for a minimum 1¾" overlap.
5. Locate the clamp at approximately ¾" from the ex end and tighten.
6. Secure the clamped outer section with three self tapping screws, drilled
equidistant, just above the clamp perimeter.
C. Routing UL1777 ex pipe.
1. Always maintain the required clearance when routing the ex vent assembly.
2. Install restop spacers (see Figure 3) when penetrating ceilings,
attic spaces, or walls.