Monessen Hearth HBDV400 Indoor Fireplace User Manual


 
54D5031 25
ROOF PITCH H (feet)
Flat to 6/12 1.0
Over 6/12 to 7/12 1.25
Over 7/12 to 8/12 1.5
Over 8/12 to 9/12 2.0
Over 9/12 to 10/12 2.5
Over 10/12 to 11/12 3.25
Over 11/12 to 12/12 4.0
*H = Minimum height from roof to lowest
discharge opening of vent.
Figure 33 - Minimum chimney clearance
VENT INSTALLATION
3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole
in roof). The 9
1
/
2
"x9
1/
2
" (241mm x 241mm) hole must be measured on the horizontal. Actual length may be larger
depending on the pitch of the roof. There must be a 1" minimum clearance from the vent pipe to combustible materials.
(Insulation should be considered a combustible material).
4. Connect a section of pipe and extend up through the hole.
NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet.
Use wall straps for this purpose. See Figure 28, page 23. Whenever possible, use 45° elbows instead of
90° elbows. The 45° elbow offers less restriction to the ow of the ue gases and intake air.
5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and
framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance
from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements.
NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep
pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing
the vent height may solve this problem.
NOTE: If the vent pipe passes through any occupied areas above the rst oor, including storage spaces
and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction
material. Make sure to meet the minimum allowable clearances to combustibles. Do not ll any of the
required clearance spaces with insulation.
CATHEDRAL CEILING INSTALLATION
1. Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box. Mark the outline of
the cathedral ceiling support box on the roof sheathing using the locating hole as a center point.
2. Cut the hole 1/8" larger than the support box outline. See Figure 32.
3. Lower the support box through the hole in the roof until the bottom of the box extends at least 2" below the ceiling. See
Figure 32. Align the support box vertically and horizontally using a level. Temporarily tack the support box in place
through the inside walls and into the roof sheeting.
4. Using tin snips, cut the support box from the top corners down to the roof line and fold the resulting flaps over the roof
sheeting. See Figure 33. Apply a bead of non-hardening, mastic around the top edges of the support box to make a seal
between the box and the roof. Nail in place with roofing nails. Remove any combustible material that might be inside
the support box.
5. Complete the cathedral ceiling installation by following the same procedures outlines in steps 2 through 6 for Flat Ceiling
Installation, page 24 and above.