Mitsubishi Electronics PE-15MYC Air Conditioner User Manual


 
- 75 -
SAFETY & CONTROL DEVICES
ITEM NO.
PE-7MYC-EU
PU-7MYC
1-EU
PE-8MYC-EU
PU-8MYC1-EU
PE-10MYC-EU
PU-10MYC1-EU
COMPRESSOR OVER CURRENT RELAY 51C 19.0A 22.0A 31.0A
COMPRESSOR INTERNAL THERMOSTAT 49C 105 ± 5 ˚C OFF 83 ± 11 ˚C ON
HIGH PRESSURE SWITCH 63H 2.94MPa OFF
INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 5.0A 3.5A 5.0A
OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2 2.5A
INDOOR FAN MOTOR INTERNAL THERMOSTAT - 150 ˚ C OFF
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT - 150 ˚C OFF
FUSE F1 3 3.15A
ITEM NO.
PE-15MYC-EU
PU-15MYC
1-EU
PE-20MYC-EU
PU-20MYC1-EU
COMPRESSOR OVER CURRENT RELAY 51C1,2 22.0A 31.0A
COMPRESSOR INTERNAL THERMOSTAT 49C
HIGH PRESSURE SWITCH 63 3.24MPa OFF
INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 4.6A 7.2A
OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2,3 2.5A
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT - 150 ˚C OFF
FUSE F1 3 3.15A
105 ± 5 ˚C OFF 83 ± 11 ˚C ON
PE-7,8,10MYC-EU
PE-15,20MYC-EU