Mitsubishi Electronics MUZ-ANA Air Conditioner User Manual


 
8
Set temperature is as shown on the right chart.
The system for dry operation uses the same refrigerant circuit as the
cooling circuit.
The compressor and the indoor fan are controlled by the room tem-
perature.
By such controls, indoor flow amounts will be reduced in order to
lower humidity without much room temperature decrease.
2-2. DRY ( ) OPERATION
95
86
77
68
59
50
°F
50 59 68 77 86 95
Set temperature
Initial room temperature
Set temperature and
initial room temperature in dry mode
°F
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
2. Indoor fan speed control
(1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto the fan speed is as follows.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
2. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
When thermostat OFF (compressor OFF), fan speed becomes Very Low.
In AUTO the fan speed is as follows.
3. Coil frost prevention
Coil frost prevention is as same as COOL mode. (2-1.3.)
The indoor fan maintains the actual speed of the moment. However ,when coil frost prevention works while the compressor
is not operating, its speed becomes the set speed.
4. Low outside temperature operation
Low outside temperature operation is as same as COOL mode. (2-1.4.)
2-3. HEAT (
) OPERATION (MSZ)
ON -1.8 °F or more
OFF less than
-1.8 °F
-1.3 °F
Room temperature minus
set temperature (During operation)
Room temperature minus
set temperature (Initial)
Thermostat
-1.8 °F
High 3.1 F or more
Med. between 1.8 and 3.1 F
Low less than 1.8 F
3.1 F
4.5 F
1.8 F
Fan speed
Room temperature minus
set temperature (Initial)
Room temperature minus
set temperature (During operation)
ON less than 3.6 °F
OFF 3.6
°F or more
3 °F
3.6 °F
Thermostat
Room temperature minus
set temperature (Initial)
Room temperature minus
set temperature (During operation)
3.6 °F
or more
Med. between 0.4 and 3.6 °F
Low
less than
0.4 °F
Fan speed
0.4 °F
3 °F
3.6 °F
7.2 °F
Room temperature minus
set temperature (During operation)
Room temperature minus
set temperature (Initial)
High