Mitsubishi Electronics MUZ-ANA Air Conditioner User Manual


 
30
3-6. OUTDOOR FAN CONTROL
Fan speed is switched according to the number of operating indoor unit and the compressor frequency.
3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera-
ture thermistor.
(1) Compressor ON/OFF
When temperature of the discharge temperature thermistor exceeds 240.8 °F, the control stops the compressor.
When temperature of the discharge temperature thermistor is 176 °F (2A/3A30NA)/ 212 °F (3A30NA-
1
/4A) or less, the
controls starts the compressor.
(2) Compressor operation frequency
When temperature of the discharge temperature thermistor is expected to be higher than 240.8 °F, the control decreases
12 Hz from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 231.8 °F and less than 240.8 °F,
the control decreases 6 Hz from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 219.2 °F and less than 231.8 °F,
the control is set at the current frequency.
Up
Down
Fan speed
High
Low
Compressor frequencyMin. Max.
3-4. HEAT DEFROSTING CONTROL
(1) Starting conditions of defrosting
When the following conditions a) ~ c) are satisfied, the defrosting starts.
a) The defrost thermistor reads 26.6 °F or less.
b) The cumulative operation time of the compressor has reached any of the set values
(31, 35, 45, 55, 65, 75, 85, 95,
105, 115, 150 minutes).
c) More than 5 minutes have passed since the start-up of the compressor.
Set value of compressor operation time (hereinafter referred to as defrost interval)
This is decided by the temperature of defrost thermistor and ambient temperature thermistor, the previous defrosting
time. For example, the first defrost interval is 40 minutes long, and the second is 45 minutes long. The third and sub-
sequent intervals are set to be longer, and less frequent, depending on defrosting time.
The third and subsequent defrost intervals follow any of the three patterns
5 or 10 to 20 minutes longer, the same,
or 5 or 10 to 20 minutes shorter compared with the previous defrost interval
with the longest 125 minutes and the
shortest 40 minutes.
(2) Releasing conditions of defrosting
Defrosting is released when any of the following conditions is satisfied:
a) The defrost thermistor continues to read 50.7 °F.
b) Defrosting time exceeds 10 minutes.
c) Any other mode than HEAT mode is set during defrosting.
NOTE : When the indoor coil thermistor is 134.6 ˚F or more on HEAT operation, fan speed is fixed to Low speed.
Or, the indoor coil thermistor is 113 ˚F or less on HEAT operation, fan speed is back to normal.
MXZ-3A30NA-
1
MXZ-4A
Number of operating
unit
Capacity code
COOL (Hz)
DRY (Hz)
HEAT (Hz)
Min. Max. Min. Max. Defrost
1
4 255825207058
7 255825207058
9,10 25 71 25 20 80 58
12 25 80 35 20 80 58
2
8 ~ 10 25 80 31 20 80 58
11 ~ 13 25 80 31 20 80 58
14 ~ 16 25 80 42 20 80 58
17 ~ 25 80 42 20 80 58
3 (MXZ-3A) 12 ~ 25 80 52 20 80 58
3 (MXZ-4A) 12 ~ 25 90 52 20 103 58
4 (MXZ-4A) 16 ~ 25 90 52 20 113 58
<Relation between compressor frequency and fan speed>
Compressor frequency (Hz)
Down Up
MXZ-2A
MXZ-3A30NA
30 40
MXZ-3A30NA
-
1
MXZ-4A
40 50