Mitsubishi Electronics MSH-A18ND Air Conditioner User Manual


 
8
SERVICE FUNCTIONS
7
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are
memorized by the indoor electronic control P.C. board. Auto restart function automatically starts operation in the same
mode just before the shutoff of the main power. However if the unit is operated in I FEEL CONTROL mode before power
failure, the operation is not memorized. In I FEEL CONTROL mode, the operation is decided by the initial room tempera-
ture.
7-3. AUTO RESTART FUNCTION
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows.
Set time : 1 minute 1-second
Set time : 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
MSH-A18ND
MSH-A24ND
Table 1
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
2 units operation
Same as at left
Solder J1
3 units operation
Same as at left
Same as at left
Solder J2
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
NOTE : For modification, take out the batteries and press the OPERATE/STOP(ON/OFF) button 2 or 3 times at first.
After modification, put back the batteries then press the RESET button.
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the
remote controller for the indoor unit.
The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they are
set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
Remote controller model : KP0A
Remote controller model : KM04A
J2
J1
J1
J2