15
Check of indoor electronic control P.C. board
C
Check the both “parts side” and “pattern
side” of indoor electronic control P.C.
board visually.
Replace the fuse.
Is fuse(F11) blown?
Replace the fan
motor.
Replace the indoor
electronic control
P.C. board.
Is winding
resistance of
fan motor 0 "?
Is winding
resistance of
vane motor 0 "?
No
Ye s
Replace the vane
motor.
Ye s
Ye s
Is varistor(NR11) burnt?
Replace the varistor.
Ye s
Turn OFF the power supply.
Remove indoor fan motor connector CN211 and
vane motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.
No
Does the unit operate with the remote controller?
Does the OPERATION INDICATOR lamp light up
by pressing the EMERGENCY OPERATION switch?
Ye s
No
Turn OFF the
power supply.
Turn OFF the
power supply.
Varistor (NR11)
Indoor electronic
control P.C. board
Fuse (F11)
No
No
The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by press-
ing the EMERGENCY OPERATION switch.
OB427B-1.qxp 07.5.16 3:30 PM Page 15