Mitsubishi Electronics MELSEC-F Fan User Manual


 
Specifications 6
6-1
6. Specifications
*1 The criterion is shown in IEC61131-2.
*2 If the pressure is higher than the atmospheric pressure, do not use FX
2N
-5A.
Malfunctions may occur.
Table 6.1: General specifications
Item Specifications
Ambient
temperature range
0 to +55
°
C during operation, -20 to +70
°
C during storage
Ambient humidity 35 to 85 % RH during operation (Dew condensation shall not be allowed.)
Vibration
resistance
*1
Frequency 10 to 57 Hz, half amplitude 0.075 mm, 57 to 150 Hz, acceleration 9.8
m/s
2
, 10 times in each of X, Y and Z directions (80 min. in each direction)
(For product installed with DIN rail: Frequency 10 to 57 Hz, half amplitude 0.035
mm, 57 to 150 Hz, acceleration 4.9 m/s
2
)
Impact resistance
*1
147 m/s
2
for 11 ms, 3 times in each of X, Y and Z directions with half-sine pulses
Noise resistance
By noise simulator of noise voltage 1,000 Vp-p, noise width 1
µ
s and frequency
30 to 100 Hz
Withstand voltage
500 V AC for 1 min
(between analog input terminal and each terminal of PLC main unit)
Insulation resistance 5 M
or more by 500 V DC Megger (between all terminals as a whole and earth)
Operating
atmosphere
Corrosive gas and much dusts shall not be detected.
Working altitude
<2000m
*2