The FX
2N
-5A analog special function block has four input channels and one output channel.
The input channels receive analog signals and converts them to the comparable digital values.
The output channel takes a digital value and outputs an equivalent analog signal.
1) Analog signal inputs can be selected from either voltage or current input. The applicable
analog signal input is set using the TO instruction supplied by the PLC main unit.
This PLC instruction is used to select different analog input signal types for each
corresponding channel.
2) The FX
2N
-5A can be connect to FX
0N
/FX
1N
/FX
2N
/FX
2NC
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
series
PLC
3) Up to 2 FX
2N
-5A units can be connected to FX
0N
main unit, FX
0N
extension unit, FX
1N
Main
unit.
Up to 8 FX
2N
-5A units can be connected to FX
2N
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
*1
Series PLC.
Up to 4 FX
2N
-5A units can be connected to one FX
2NC
Series PLC.
For connection to the FX
2NC
Series PLC, an FX
2NC
-CNV-IF is required.
For connection to the FX
3GC
/FX
3UC
Series PLC, an FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is
required.
Data transfer with the PLC is performed via buffer memories of the FX
2N
-5A using FROM/
TO Instructions.
*1 Up to 7 units can be connected to an FX
3UC
-32MT-LT(-2) PLC.
FX2N-5A Special function block