Lochinvar 400-801 Boiler User Manual


 
1 Service
16
1 Service
Parameter table
Service Manual
Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where
to access them
Menu Description
See
Page
User Access Installer Access
Display Modify Display Modify
Outdoor 1 Low 21 No No Yes Yes
Outdoor 1 High 21 No No Yes Yes
Set Point 1 at Low Outdoor Temp 1 21 No No Yes Yes
Set Point 1 at High Outdoor Temp 1 21 No No Yes Yes
Outdoor Air Shutdown SH1 21 No No Yes Yes
Outdoor Air Shutdown Differential SH1 22 No No Yes Yes
Shift Reset Curve SH1 22 No No Yes Yes
Outdoor 2 Low 21 No No Yes Yes
Outdoor 2 High 21 No No Yes Yes
Set Point 2 at Low Outdoor Temp 2 21 No No Yes Yes
Set Point 2 at High Outdoor Temp 2 21 No No Yes Yes
Outdoor Air Shutdown SH2 21 No No Yes Yes
Outdoor Air Shutdown Differential SH2 22 No No Yes Yes
Shift Reset Curve SH2 22 No No Yes Yes
Outdoor 3 Low 21 No No Yes Yes
Outdoor 3 High 21 No No Yes Yes
Set Point 3 at Low Outdoor Temp 3 21 No No Yes Yes
Set Point 3 at High Outdoor Temp 3 21 No No Yes Yes
Outdoor Air Shutdown SH3 21 No No Yes Yes
Outdoor Air Shutdown Differential SH3 22 No No Yes Yes
Shift Reset Curve SH3 22 No No Yes Yes
Boost Temperature 22 No No Yes Yes
Boost Time 22 No No Yes Yes
Anti-Cycling Time 22 No No Yes Yes
Anti-Cycling Override Differential 22 No No Yes Yes
Ramp Delay 22 No No Yes Yes
Ramp Settings 23 No No Yes Yes
OUTDOOR RESET
ANTI-CYCLING