Lochinvar 2.5 Boiler User Manual


 
1 Service (continued)
Service Manual
15
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them
Menu
Sub
Item
Parameter Name
(as shown on the LCD screen)
See
Page
Min
Max
Default
User Installer
Value Value Value Access Access
F
1 Temperature Units 21 °F °C °F Yes Yes
2 LCD Backlight Time 21 0 255 240 Yes Yes
3 Freeze Protection; Pump On 21 -22 45 44.6 No Yes
4 Freeze Protection; Burner On 22 -22 45 37.4 No Yes
5 Freeze Protection; Burner Diff 22 0 20 5 No Yes
6 HWG to SH Switching Time 22 0 240 30 No Yes
7 SH to HWG Switching Time 22 0 240 30 No Yes
8 Anti-Cycling Time 22 0 40 10 No Yes
9 Anti-Cycling Differential 22 0 40 1 No Yes
10 HWG Rate Limiting 22 10 100 100 No Yes
11 Service Mode Timeout 22 0 40 40 No Yes
12 Controlling Sensor 22 0 4 2 No Yes
13 Inlet Control Time Delay 22 0 40 3 No Yes
G
1 SH Night Setback Offset Temp 22 0 90 0 No Yes
2 SH Night Setback Mon End 22 N/A N/A N/A No Yes
3 SH Night Setback Mon Begin 22 N/A N/A N/A No Yes
4 SH Night Setback Tue End 22 N/A N/A N/A No Yes
5 SH Night Setback Tue Begin 22 N/A N/A N/A No Yes
6 SH Night Setback Wed End 22 N/A N/A N/A No Yes
7 SH Night Setback Wed Begin 22 N/A N/A N/A No Yes
8 SH Night Setback Thur End 22 N/A N/A N/A No Yes
9 SH Night Setback Thur Begin 22 N/A N/A N/A No Yes
10 SH Night Setback Fri End 22 N/A N/A N/A No Yes
11 SH Night Setback Fri Begiin 22 N/A N/A N/A No Yes
12 SH Night Setback Sat End 22 N/A N/A N/A No Yes
13 SH Night Setback Sat Begin 22 N/A N/A N/A No Yes
14 SH Night Setback Sun End 22 N/A N/A N/A No Yes
15 SH Night Setback Sun Begin 22 N/A N/A N/A No Yes
ADVANCED SETUP
SH NIGHT SETBACK