Lochinvar 2.5 Boiler User Manual


 
1 Service
Service Manual
16
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them
Menu
Sub
Item
Parameter Name
(as shown on the LCD screen)
See
Page
Min
Max
Default
User Installer
Value Value Value Access Access
H
1 HWG Night Setback Offset Temp 22 0 90 0 No Yes
2 HWG Night Setback Mon End 22 N/A N/A N/A No Yes
3 HWG Night Setback Mon Begin 22 N/A N/A N/A No Yes
4 HWG Night Setback Tue End 22 N/A N/A N/A No Yes
5 HWG Night Setback Tue Begin 22 N/A N/A N/A No Yes
6 HWG Night Setback Wed End 22 N/A N/A N/A No Yes
7 HWG Night Setback Wed Begin 22 N/A N/A N/A No Yes
8 HWG Night Setback Thur End 22 N/A N/A N/A No Yes
9 HWG Night Setback Thur Begin 22 N/A N/A N/A No Yes
10 HWG Night Setback Fri End 22 N/A N/A N/A No Yes
11 HWG Night Setback Fri Begin 22 N/A N/A N/A No Yes
12 HWG Night Setback Sat End 22 N/A N/A N/A No Yes
13 HWG Night Setback Sat Begin 22 N/A N/A N/A No Yes
14 HWG Night Setback Sun End 22 N/A N/A N/A No Yes
15 HWG Night Setback Sun Begin 22 N/A N/A N/A No Yes
I
1 ModBus Active / Inactive 23 ACTIVE INACTIVE INACTIVE No Yes
2 ModBus Out of Order Timer 23 5 120 30 No Yes
J
1 Cascade Active / Inactive 23 ACTIVE INACTIVE INACTIVE No Yes
2 Cascade Address 23 0 7 1 No Yes
3 Cascade Offset 23 0 40 10 No Yes
4 Cascade Differential 23 0 72 20 No Yes
5 Max Boiler Setpoint for Cascade 23 32 185 185 No Yes
6 Cascade Type 23 N/A N/A N/A No Yes
7 Block Time Switching Boiler On / Off 23 0 255 60 No Yes
8 Minimum Next On Time 24 0 255 60 No Yes
9 Rate % to Switch On Next Boiler 24 1 100 80 No Yes
10 Rate % to Switch Off Last Boiler 24 1 100 10 No Yes
11 Number of Boiler Pumps Always On 24 0 8 0 No Yes
HWG NIGHT SETBACK
CASCADE
MOD