Lochinvar 150 - 500 Water Heater User Manual


 
3 Troubleshooting
24
Service Manual
Table 3D Troubleshooting Chart - Noisy System
FAULT CAUSE CORRECTIVE ACTION
Noisy
Operation
- Supply gas problem. Natural gas pressures
should be between 4 inches w.c. and
14 inches w.c. LP gas pressures should
be between 8 inches w.c. and
14 inches w.c.
• Refer to Section 7 - Gas Connections of the Armor
Water Heater Installation and Operation Manual for
detailed information concerning the gas supply.
- Gas/air mixture problem.
• Refer to the Gas Valve Adjustment Procedure on
page 33 of this manual for the proper gas valve setting.
Verify that the vent/air intake lengths do not exceed the
maximum listed in the General Venting section of the
Armor Water Heater Installation and Operation Manual.
- Dirty/damaged burner.
Refer to page 19 in this manual for the burner removal
and inspection procedure. Clean or replace the burner
as necessary.
- Low water flow through the heat exchanger.
Refer to Section 6 - System Piping of the Armor Water
Heater Installation and Operation Manual for minimum
flow rates.
- Air in the piping system. • Properly purge all air from the piping system.
- Low system water pressure. • Verify system pressure is a minimum of 12 PSI.
No Pump
Operation
- Blown fuse.
Replace fuse F5 on the control board, see page 21 of
this manual.
- Faulty pump. • Replace pump.
- Faulty pump relay. • Replace pump relay.
- Internal fault on control board. • Replace main control board.
Relief Valve
Opening
- System pressure exceeds relief valve
setting.
Lower the system pressure below the 150 PSI rating of
the supplied relief valve.
APS
Open
(will require a
manual reset once the
condition has been
corrected. Press the
RESET button on the
SMART SYSTEM
display to reset.)
Air pressure switch contacts are open.
Check the wiring connections to switch. Wires should
be connected to the common and normally closed
terminals.
Air intake lengths exceed the maximum allowed
lengths. Refer to Section 3 - General Venting of the
Armor Water Heater Installation and Operation Manual
for proper lengths.
Check for obstruction or blockage in the air
intake pipes or at terminations.
Check reference hoses connected to the air pressure
switch for blockage or obstruction.
• Inspect the burner. Reference page 19 of this manual
for removal and cleaning procedures. Replace if
necessary.
Inspect the heat exchanger. Reference page 20 of this
manual for removal and cleaning procedures. Replace
if necessary.
Faulty air pressure switch. Replace switch.