Lochinvar 150 - 500 Water Heater User Manual


 
22
Service Manual
3 Troubleshooting
Table 3A Troubleshooting Chart - No Display
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit. Check external line switch, fuse, or breaker.
Check position of ON/OFF switch. Turn switch to the
ON position.
Check 120 VAC through the ON/OFF switch.
Check wiring harness connection between display
board and main control board. Connect
harness at both points.
- No voltage through the switch. Replace switch.
- Bad display board. Replace board.
- Bad main control board. Replace the main control board.
- Blown fuse. Replace fuse F3 on the main control board, see
page 21 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
Review temperature setting.
- Remote thermostat satisfied. Review remote thermostat setting.
- Unit locked out on fault. • Consult display for specific fault. Refer to fault
descriptions on page 25 of this manual for corrective
actions.
Unit Does Not
Modulate Above
50%
- Water heater controlled by BMS.
Check BMS parameter settings. Optional PC software
required.
- Flue sensor open.
Verify that the flue sensor is located in the flue outlet.
Check wiring connections at the flue sensor.
Check the resistance of the flue sensor and compare
to Table 3C on page 23 of this manual.