Lenox Elite Series X16 Air Conditioner Units Air Conditioner User Manual


 
Page 28
506637−01 11/10
Accessories
For update−to−date information, see any of the following
publications:
S Lennox XC16 Engineering Handbook
S Lennox Product Catalog
S Lennox Price Book
Checklists
Two−Stage Modulation Compressors Field Operational Checklist
Unit Readings Y1 − First-Stage
Expected results during Y2
demand (Toggle switch On)
Y2 − Second-Stage
COMPRESSOR
Voltage Same
Amperage Higher
OUTDOOR UNIT FAN
MOTOR
Amperage Same or Higher
TEMPERATURE
Ambient Same
Outdoor Coil Discharge Air Higher
Compressor Discharge Line Higher
Indoor Return Air Same
Indoor Coil Discharge Air Lower
PRESSURES
Suction (Vapor) Lower
Liquid Higher
Start−Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? - Indoor Filter clean? - Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Discharge Pressure Suction Pressure Refrigerant Charge Checked? -
Refrigerant Lines: Leak Checked? - Properly Insulated? - Outdoor Fan Checked? -
Service Valves: Fully Opened? - Caps Tight? - Thermostat
Voltage With Compressor Operating Calibrated? - Properly Set? - Level? -