Lennox International Inc. Touch Screen Programmable Communicating Thermostat Thermostat User Manual


 
icomfortt Touch Screen 7−Day Programmable Thermostat
Page 27
Parameter Name: IncrementParameter Value SettingDefault
AIR HANDLER
Equipment Name Air Handler (Typewriter input screen) Ċ
Electric Heating Airflow
nnnn CFM
SEE NOTE −.
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
5CFM
Low Cooling Airflow 5CFM
High Cooling Airflow 5CFM
Cooling Airflow Profile 1
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min; OFF:50%/30s
Ċ
Low Heating Airflow
nnnn CFM
SEE NOTE −.
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
5CFM
High Heating Airflow 5CFM
Continuous Indoor Blower Airflow 10CFM
Humidification Airflow 10CFM
Dehumidification Airflow 70% 60 to 80% (percentage of reduction of High Cooling Airflow) 1%
Heating Indoor Blower OFF Delay 10 sec 0 to 10 Seconds 1 sec
Heating Indoor Blower ON Delay 0 sec 0 to 5 Seconds 1 sec
Cooling Indoor Blower OFF Delay 0 sec 0 to 30 Seconds 2 sec
Cooling Indoor Blower ON Delay 2 sec 0 to 10 Seconds 1 sec
HP Indoor Blower OFF Delay 45 sec 0 to 60 Seconds 5 sec
HP Indoor Blower ON Delay 0 sec 0 to 30 Seconds 5 sec
THERMOSTAT
Equipment Name Ċ (Typewriter input screen) Ċ
Temp Reading Calibration 0ºF −5ºF to 5ºF 1ºF
Humidity Reading Calibration 0% −10 to 10% 1%RH
OUTDOOR EQUIPMENT
Equipment Name (HP and AC) Outdoor Unit (Typewriter input screen = up to 35 characters in string) Ċ
Compressor Short Cycle Delay (HP and AC) 300 Seconds 60 to 300 Seconds 60 Sec
Compressor Shift Delay On/Off (HP only) On On, Off Ċ
Defrost Termination Temp (HP only) 50ºF 50 to 100ºF 10ºF