Lennox International Inc. SLP9801 Thermostat User Manual


 
506920−01 09/12
Page 64
Configuring heat strips on Air Handler Control (AHC)
IMPORTANT: After electric heat strips are installed, the Air Handler Control
(AHC) must be manually configured to detect the number of electric heat
sections. (SEE ALSO 506181−01 for complete configuration guide.)
To configure the heat strips so that they will be detected by the thermostat:
S Power must be applied to the air handler but NOT to the thermostat.
Remove thermostat from baseplate or remove wires to thermostat at
the air handler.
S On the air handler control (AHC), unit should be in idle mode (decimal
blinks at 1 HertzĊ0.5 second ON, 0.5 second OFF.
S Select field test modeĊpress and hold the pushbutton until solid –"
appears; release button. Display will blink.
S Press the pushbutton and wait for the display LED to show H" (capital
H), then release the button.
S The AHC cycles the indoor blower motor on" to the selected heat
speed and stages the electric heat relays on" and off" to automatically
detect the number of electric heat sections. The AHC stores the num-
ber of electric heat sections, then automatically exits Field Test
Mode".
S At this point, the icomfort Wi-Fit will now detect the heat strip informa-
tion stored in the AHC.
OUTDOOR
AIR SENSOR
HEAT
1234
COOL
1234
DELAY
1234
ADJUST
NORM +
HUMIDIFICATION
SMART
AUTO
EVENHEAT
1234
BLOWER
ONLY CFM
100
11 5
130
85
Y1Y2
2STAGE
COMPR
RO
HEAT
PUMP
RDS
DEHUM
OR
C
W1
W2
G
Y2
Y1
C
R
DH
H
L
O
DS
W3
FUSE 3 AMP
XFMR 24V
24 VAC
COM
3
6
9
1
4
7
XFMR LINE
G
2
5
8
P8
L1
L2
L2 L1
INDOOR
BLOWER
POWER
EARTH
INDOOR BLOWER
SIGNAL
4
5
6
12 3
A92
INTEGRATED
CONTROL
OUTDOOR UNIT
LINK
I + I
I + I RC
I + I
R
C
THERMOSTAT
HUMIDITROL
DH
DISCHARGE
AIR SENSOR
HARMONY
PUSHBUTTON LED