Lennox International Inc. MERIT SERIES GAS FURNACE DOWNFLOW AIR DISCHARGE Electric Heater User Manual


 
Page 25
FIGURE 35
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(Field Furnished)
5” (127 mm)
51/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
WALL SUPPORT*
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSECOUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
6” (152 mm)
Maximum
8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe
between the end of the exhaust pipe and intake pipe
8” (203 mm) Min.
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
If intake and exhause pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field
fabricated piping must be installed.
FIGURE 36
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(Field Furnished)
5” (127 mm)
51/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
WALL SUPPORT*
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSECOUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada)
3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
6” (152 mm)
Maximum
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
6” (152 mm)
Minimum
6” (152 mm)
Minimum
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
If intake and exhause pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field
fabricated piping must be installed.