Lennox Hearth MPB35ST-NM-B Indoor Fireplace User Manual


 
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Gas Valve Diagrams
See Figure 1 for Millivolt models and Figure 2
For Electronic Models.
Figure 2 - Honeywell Electronic Gas Valve
FFO
NI
P
S
I
NO
LORTNOC
GI NTI ER
Manifold Pressure
Port
ON / OFF Switch
Inlet
Pressure
Port
Electronic Gas
Control Valve
H
I
L
O
W
HTPTHTPT
P
I
L
O
T
P
I
L
O
T
O
N
it
O
F
F
IN
OUT
Manifold Pressure Tap
Inlet Pressure Tap
Pilot Adjustment
Screw
HI/LO Variable
Flame Height
Adjustment
Main Gas
Control Knob
OFF/PILOT/ON
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
Nat.Gas
drill size (inches)
Propane
drill size (inches)
MPB35ST-B
#37 (.104")
*
24M1001 •
1.55
mm
(.061")
*
42M7901 •
Table 5
Orifice Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard
burner orifice sizes (marked with an "*" in Table
5). For elevations above 4500 feet, contact your
gas supplier or qualified service technician.
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
Using gas that has been derated by the gas
company.
Changing the burner orice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition or, in Canada, the CAN/CSA-B149.1
codes - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or, in Canada,
the CAN/CSA-B149.1 - latest edition.
NOTE: Flame appearance will diminish 4% per
thousand feet.
* Standard size installed at factory
• Part /Cat. Number
Figure 1 - SIT Millivolt Gas Valve
REQUIREMENTS FOR THE COMMON-
WEALTH OF MASSACHUSETTS
Installation of these fireplaces are approved
for installation in the US state of Massachu-
setts if the following additional requirements
are met:
Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R. Sec. 5.08 2(a) through 2(e).
Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
The exible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
The individual manual shut-off must be a
T-handle type valve.
NEW YORK CITY, NEW YORK (MEA)
Installation of these fireplaces are approved
for installation in New York City in the US state
of New York.
Gas Pressure - All Models
Tables 3 and 4 show the units' gas pressure
requirements:
Inlet Gas Supply Pressure
(all models)
Fuel # Minimum Maximum
Natural Gas
5.0" WC
(1.24 kPa)
10.5" WC
(2.61 kPa)
Propane
11.0" WC
(2.74 kPa)
13.0" WC
(3.23 kPa)
Table 3
Manifold Gas Supply Pressure
(all models)
Fuel # Low
(millivolt only)
High
Natural
Gas
(Lo) 2.2" WC
(0.55 kPa)
(Hi) 3.5" WC
(0.87 kPa)
Propane
(Lo) 6.3" WC
(1.57 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 4
Test gauge connections are provided on the
front of the millivolt gas control valve, identi-
fied IN for the inlet and OUT for the manifold
side. A 1/8" NPT Test gauge connection
is provided at the inlet and outlet side of
the electronic gas control valve.
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
These appliances must be isolated from the
gas supply piping system (by closing their
individual manual shut-off valve) during any
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure
testing of that system at pressures greater
than 1/2 psig (3.5 kPa).
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.