Lennox Hearth II-T C INS Stove User Manual


 
PLANNING YOUR INSTALLATION
PAGE 8
MANUFACTURED (MOBILE) HOME INSTAL-
LATION
Freestanding Model – Advantage II-T C FS
In addition to the standard installation instructions,
the following instructions may be required by lo-
cal, state or federal building codes:
Stove must be permanently bolted to the floor.
An outside air inlet must be provided for com-
bustion and be unrestricted while unit is in use.
Use a galvanized or stainless steel pipe for the
duct (the outside air inlet on the stove is 1 5/8"
diameter).
Stove must be permanently electrically
grounded to the steel chassis of the home. The
location selected for ground attachment to the
stove must be dedicated for this purpose.
See pages 13 through 18 for additional informa-
tion on venting requirements.
Do not install appliance in a sleeping room.
The structural integrity of the manufactured
home floor, walls, ceiling and roof must be
maintained.
NOTE: The grounding of this product, at installa-
tion, must comply with NFPA-70 stan-
dards, CSA C22.1 in Canada, as well as
any local codes.
Model – Advantage II-T C FS
Pedestal Air Inlet
MANUFACTURED (MOBILE) HOME EXHAUST VENT PIPE
INSTALLATION GUIDELINES
Use only “PL” pellet vent pipe listed to UL 641 and ULC
S609. The pipe should extend at least 3 feet above the part
of the roof through which it passes. The top of the pipe
should be at least 2 feet above the highest required elevation
of any part of the manufactured (mobile) home within 10 feet
of the pipe (see page 14, Manufactured [Mobile] Home
Chimney Height Requirements).
If the exhaust vent exits the manufactured (mobile) home at a
location other than the roof, and exits at a point 7 feet or less
above the ground level on which the manufactured (mobile)
home is position a guard or method of enclosing the pipe
shall be provided at the point of exit for a height of up to 7
feet. The openings, if any, in this guard shall not allow a 3/4”
rod to pass through. A 1/2” rod could pass through but should
not be able to touch the pipe when inserted through the open-
ing a distance of 4 inches.
24 ¾”
12 ½”
6 7/8”
25”
Outside Air Inlet
1 5/8" diameter
Bolt
Bolt
Floor Protector
Steel Chassis
Ground
To Chassis
Floor
www.PelletKing.com