Lennox Hearth EPIC33 Stove User Manual


 
5
Inspection
The state or local gas inspector of the side wall horizontally vented gas
fueled equipment shall not approve the installation unless, upon inspection,
the inspector observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
The equipment listed in Chapter 10 entitled “Equipment Not Required
To Be Vented” in the most current edition of ANSI Z233.1 / NFPA 54
(In Canada CAN/CSA B149.1 - current edition) as adopted by the
Board; and
Product Approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building
or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented
gas equipment provides a venting system design or venting system com
-
ponents with the equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system shall include:
Detailed instructions for the installation of the venting system design
or the venting system components; and
A complete parts list for the venting system design or venting sys
-
tem.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally
vented gas fueled equipment does not provide the parts for venting the
flue gases, but identifies “special venting systems”, the following require
-
ments shall be satisfied by the manufacturer:
The referenced “special venting system” instructions shall be included
with the appliance or equipment installation instructions; and
The “special venting systems” shall be Product Approved by the
Board and the instructions for that system shall include a parts list
and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall
horizontally vented gas fueled equipment, all venting instructions, all
parts lists for venting instructions and/or all venting design instructions
shall remain with the appliance or equipment at the completion of the
installation.
Installation and repair must be done by a plumber or gas fitter licensed
in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92
centimeters) in length.
The individual manual shut-off must be a T-handle type valve.
New York City, New York (MEA)
Installation of these fireplaces are approved for installation in New York
City in the US state of New York (MEA#: 138-07-E).
Commonwealth Of Massachusetts Require-
ments
Note: The following requirements reference various Massachusetts
and national codes not contained in this document.
For all side wall horizontally vented gas fueled equipment installed in every
dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and
where the side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but not limited
to decks and porches, the following requirements shall be satisfied:
Installation Of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gas-fitter shall observe that a hard
wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed.
In addition, the installing plumber or gas-fitter shall observe that a bat
-
tery operated or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall
be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon
monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment
is installed in a crawl space or an attic, the hard wired carbon monoxide
detector with alarm and battery back-up may be installed on the next
adjacent floor level.
In the event that the requirements of this subdivision can not be met
at the time of completion of installation, the owner shall have a period
of thirty (30) days to comply with the above requirements; provided,
however, that during said thirty (30) day period, a battery operated
carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to
the exterior of the building at a minimum height of eight (8) feet above
grade directly in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The sign shall read, in
print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”