Jotul Woodstove F 400 Stove User Manual


 
18
Parts list for the Jøtul F 400
woodstove
Consult your dealer for part numbers and
replacement parts.
1 Ashlip
2 Door
2A Gasket
2B Glass clips
3B Latch
4 Right side panel
5 Front panel
6 Top casting
7 Upper back panel
8 Smoke outlet
9 Back panel
10 Left side panel
11 Leg (long leg)
12 Upper bottom panel
13 Front door handle
14 Right burn plate
15 Glass panel
16 Airchamber
17 Air wash manifold
18 Top baffle (stainless steel)
19 Baffle cover (cast iron)
20 Air inspection cover
21 Rear burn plate
22 Fire brick (3)
23 Bottom grate
24 Left burn plate
25 Lower bottom panel
26 Ashpan housing
* Ashpan
27 Air slider/valve
28 Air devider
30 Air control lever (chrome)
Allen head screw
31 Ashpan door
* Ashpan door pin
32 Ash door handle
33 Baffle plate II
34 Latch compl.
* Not shown
Appendix A
Alternate floor protection
All floor protection materials must be non-combustible ie. metal,
brick, stone, mineral fiber boards). Any combustible material may
not be used.
The easiest means of determining if a proposed alternate floor
material meets requirements listed in this manual is to follow this
procedure.
R-value = thermal resistance
k-value = thermal conductivity
C-value = thermal conductance
1. Convert the specification to R-value;
a. If R-value is given, no conversion is needed.
b. If k-value is given with a required thickness (T) in inches:
R=1/k X T.
c. If C-value is given: R=1/C.
2. Determine the R-value of the proposed alternate floor protector.
a. Use the formula in Step 1 to convert values not expressed
as “R”.
b. For multiple layers, add R-values of each layer to determine
overall R-value.
3. If the overall R-value of the sustem is greater than the R-value of
the specified floor protector, the alternate is acceptable.
Example:
The specified floor protector should be 3/4” thick material with a k-
factor of 0.84. The proposed alternate is 4” brick with a C-factor of
1.25 over 1/8” mineral board with a k-factor of 0.29.
Step A. Use formula above to convert specifications to R-value. R=1/
k X T= 1/.84 X .75 = .893
Step B. Calculate R of proposed system.
4” brick of C-1.25, therefore
R brick = 1/C = 1/1.25 = 0.80.
1/8” mineral board of k = 0.29 therefore
R mineral board = 1/.29 X 0.125 = 0.431
Total R = R brick + R mineral board=
0.8 + 0.431=1.231
Step C. Compare proposed system R = 1.231 to specified R of 0.893.
Since R is greater than required, the system is acceptable.
Definitions:
Thermal conductance =
C = Btu = W
(hr)(ft
2
)(F) (m
2
)(K)
Thermal conductivity =
k = Btu = W = (Btu)
(hr)(ft
2
)(F) (m
2
)(K) (hr)(ft)(F)
Thermal resistance=
R = Btu = (m
2
)(K) = (Btu)(inch)
(hr)(ft
2
)(F) W (hr)(ft
2
)(F)
The Jøtul F 400 Castine woodstove requires floor protection with a
minimum insulating r value of 0.5.
Alcove installation require a minimum r value of 1.6. (If a ul/ulc or
whi listed hearth pad is not used.)
USA/Canada