Type 05
Trouble by Day/
Alarm by Night
• Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone
covering a sensitive area such as a stock room, drug supply room, etc.
• Can also be used on a sensor or contact in an area where immediate notification of an entry is
desired.
• Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay, Instant or
Maximum (night) modes.
• During the disarmed state (day), the system will provide a latched trouble sounding from the
keypad (and a central station report, if desired).
Type 06
24-hr Silent Alarm
• Usually assigned to a zone containing an emergency button.
• Sends a report to the central station but provides no keypad display or sounding.
Type 07
24-hour Audible
Alarm
• Assign to a zone that has an emergency button.
• Sends a report to the central station, and provides an alarm sound at the keypad, and an
audible external alarm.
Type 08
24-hour
Auxiliary Alarm
• Assign to a zone containing an emergency button, or to a zone containing monitoring devices
such as water or temperature sensors.
• Sends a report to the central station and provides an alarm sound at the keypad. (No bell
output is provided.)
Type 09
Supervised Fire
• Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm
produces a pulsing bell output.
• This zone type is always active and cannot be bypassed.
Type 10
Interior w/Delay
• Provides entry delay (using the programmed entry time), if tripped when the panel is armed in
the Away mode.
• Entry Delay 1 begins whenever sensors in this zone are violated, regardless of whether or not
an entry/exit delay zone was tripped first.
• Bypassed when the panel is armed in the Stay or Instant modes; if armed in Night-Stay mode,
zones assigned to zone list 05 (night-stay zone list) are not bypassed when system armed in
Night-Stay mode.
Type 12
Monitor Zone
• Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a short/open, the
message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent
to the Central Station. The system keypad will display a “check” message indicating the
appropriate zone (but keypad beeping does not occur). Upon restoral of the zone, the message,
"*RESTORE*-24 Hr. Non-Burg. -#XXX " will be sent to the Central Station.
• The “check” message will automatically disappear from the keypad dynamically, when the
zone restores; a user code + off sequence is not needed to reset the zone.
• Faults of this zone type are independent of the system, and can exist at the time of arming
without interference.
• Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon
“alarm.”
Type 14
24 Hour Carbon
Monoxide
Monitor
• Assigned to any zone with a carbon monoxide detector.
• The bell output will pulse when this zone type is alarmed.
• Always active and cannot be bypassed.
Type 16
Fire
w/Verification
• Provides a fire alarm when zone is shorted, but only after alarm verified.
• System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent
short circuit within 90 seconds triggers fire alarm.
• Provides a trouble response when zone is open.
Type 20
Arm-Stay (BR
only)
• Arms the system in Stay mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User number for button must be assigned.
Type 21
Arm-Away (BR
only)
• Arms the system in Away mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User number for button must be assigned.
Type 22
Disarm (BR only)
• Disarms the system when the zone is activated.
• User number for button must be assigned.