Honeywell VISTA-15PSIA Home Security System User Manual


 
SECTION 5
Menu Mode Programming
Zones and Partitions
Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode
or
58 Expert Programming Mode.
The VISTA-20P system can control two independent areas of protection (known as partitions) for use by
independent users, if desired, by simply assigning zones to one or the other partition during zone
programming. The VISTA-20P, by default, automatically distributes users between the two partitions. The
master user can change the user number distributions.
Zones can also be assigned to a common partition, which is an area shared by users of both partitions (such
as a lobby in a building). This allows either partition to arm, while leaving the common partition disarmed
for access into the other partition. The following describes the functioning of the VISTA-20P common
partition:
• The common zone sounds and reports alarms only when both partitions are armed. If only one partition
is armed, the system ignores faults on the common zone.
• Either partition may arm its system if the common zone is faulted, but once armed, the other partition
will not be able to arm unless the common zone is first bypassed or the fault is corrected.
• Faults on the common zone are displayed on common zone keypads, and will also appear on another
partition’s keypad when that partition is armed.
• Either partition can clear and restore the common zone after an alarm.
About Zone Programming (
56 and
58 Menu Modes)
Used to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter serial numbers,
and identify the type of loop input device(s).
Can also be used to enter alpha descriptors for programmed zones; however, we recommend entering
descriptors in menu mode
82 (Alpha Descriptor Programming after all zone programming has been
completed).
*58 Expert Programming mode provides a faster method of zone programming than *56 Menu mode, but
is recommended only for those who have had previous experience in programming controls of this type.
NOTE: Alpha display prompts are shown in a double-line box.
56 Zone Programming Procedure
1. Enter the zone number to be programmed.
2. Make appropriate entries at the prompts.
3. Confirm the serial number of wireless transmitter zones.
Start Zone Programming mode by pressing
56 while in Data Programming mode.
SET TO CONFIRM?
0 = NO 1 = YES
Set to Confirm
0 = no; 1 = yes
If 1 (Yes) is entered, you will be prompted to confirm each transmitter after entering the
serial and loop numbers (at the “XMIT TO CONFIRM” prompt later in this procedure). We
recommend that you confirm the programming of every transmitter.
5-1