Honeywell TH8110U Thermostat User Manual


 
TH8110U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
69-1700 10
Table 6. Advanced Settings Menu.
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Furnace Filter
Change
Reminder
0500 0 Furnace filter
change reminder
off
1-6 1—10 r u n t i m e d a y s
2—30 ru n t i m e d a y s
3—60 ru n t i m e d a y s
4—90 ru n t i m e d a y s
5—1 2 0 r u n t i m e d a y s
6—3 6 5 r u n t i m e d a y s
Run time based on
call for fan.
Humidifier Pad
Replacement
Reminder
0510 0 Humidifier pad
replacement
reminder off
1-3 1—90 calendar days
2—180 calendar days
3—365 calendar days
UV Lamp
Replacement
Reminder
0520 0 UV Lamp
replacement
reminder off
1 1—365 calendar days
Adaptive
Intelligent
Recovery™
0530 1 Adaptive
Intelligent
Recovery™
control is
activated (system
starts early so
setpoint is
reached by start
of program
period).
0 0—conventional
recovery (system starts
recovery at
programmed time)
Number of
Periods
0540 4 Four periods
available (Wake,
Leave, Return,
Sleep)
2 Two periods availbable
(Wake and Sleep)
Not shown in non-
programmable is
selected. 2 or 4
applies to all days of
the week.
Minimum
Compressor
Off Time
0580 5 Five minute
minimum off time
for compressor
0, 2, 3, 4 Minimum number of
minutes compressor is
off between calls for
compressor
Heat
Temperature
Range Stop
0600 90 Highest heating
setpoint.
40 to 89 Temperature range (1°F
increments) of heating
setpoint.
Shown in 1/2 °C.
Cool
Temperature
Range Stop
0610 50 Lowest cooling
setpoint.
51 to 99 Temperature range (1°F
increments) of cooling
setpoint.
Shown in 1/2 °C.
Clock Format 0640 12 12-hour clock
format
24 24-hour clock format
Extended Fan
on time Heat
0650 0 No extended fan
operation after
call for heat ends
90 Fan operation is
extended 90 seconds
after call for heat ends.
Not shown if fan
operation is set to
fossil fuel or in Cool
Only Systems
Extended Fan
on time Cool
0660 0 No extended fan
operation after
call for cool ends
90 Fan operation is
extended 90 seconds
after call for cool ends.
Not shown in Heat
Only Systems.