BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
25 63-4524—01
BV75 Value MV52 Index MV27 Object
Name
Function MV26 State Text Index Default Value
On/Off 1 (2 pipe) Heat/Cool Valve
Status
1 Closed – 2 Open Closed
2 (4 pipe) Cooling Valve
Status
1 Closed – 2 Open Closed
Floating 1 (2 pipe) Heat/Cool Valve
Status
1 Stopped - 2 Opening - 3 Closing Stopped
2 (4 pipe) Cooling Valve
Status
1 Stopped - 2 Opening - 3 Closing Stopped
Table 10. Property enumeration sets for MV objects. (Continued)
Object Name Object ID BACnet Index Text Default value
BI1 Configuration MV 46
1None
None
2Rem NSB
3 Motion NO
4 Motion NC
5 Window
BI2 Configuration MV 47
1None
None
2Door Dry
3 Override
4Filter
5 Service
UI3 Configuration MV 48
1None
None
2COC/NH
3COC/NC
4COS
5SS
Pipe Number MV 52
1 2 Pipe 4 Pipes
24 Pipe
Out#1 Cfg MV 53
12 4
24
AUX Configuration MV 54
1 Not used
Not Used
2 NO with Occ
3 NC with Occ
4 NO with Occ & Fan
5 NC with Occ & Fan
6 Network controlled