BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
17 63-4524—01
Objects Table
Table 5. Objects.
Object Name
Type and
Instance
Object Property
TB7200C5x14B
TB7200F5x14B
TB7300A5x14B
TB7305A5x14B
TB7300C5x14B
TB7305C5x14B
TB7350C5x14B
TB7355C5x14B
TB7300F5x14B
TB7305F5x14B
TB7350F5x14B
TB7355F5x14B
Room Temperature AV 7 Present_Value (R,W)

Room Temp Override BV 8 Present_Value (R,W)

Outdoor Temperature AV 9 Present_Value (R,W)

Room Humidity AV 10 Present_Value (R,W)
 
Room Humid Override BV 11 Present_Value (R,W)
 
Supply Temperature AI 12 Present_Value (R)

Dehumidification
Lockout
BV 13 Present_Value (R,W)
 
AUX Command BV 14 Present_Value (R,W)

Sequence of Operation MV 15 Present_Value (R,W)

System Mode MV 16 Present_Value (R,W)

Fan Mode MV 17 Present_Value (R,W)

Occupancy Command MV 18 Present_Value (R,W)

Keypad Lockout MV 19 Present_Value (R,W)

Control Output GRP 20 Present_Value (R)
PI Heating Demand AV 21 Present_Value (R)

PI Cooling Demand AV 22 Present_Value (R)

Dehumidification Status BI 23 Present_Value (R)
 
Controller Status GRP 24 Present_Value (R)
AUX Status BI 25 Present_Value (R)

Heating Valve Status MV 26 Present_Value (R)

Cooling Valve Status MV 27 Present_Value (R)

Fan Status MV 28 Present_Value (R)

BI 1 Status BI 29 Present_Value (R)

BI 2 Status BI 30 Present_Value (R)

UI 3 Status BI 31 Present_Value (R)

Local Motion BI 32 Present_Value (R)

Effective Occupancy MV 33 Present_Value (R)

Controller Alarms GRP 34 Present_Value (R)
Window Alarm BI 35 Present_Value (R)
