Property Enumeration Sets for BV & BI Objects
Table 9. Property enumeration sets for BV and BI objects.
(**) This object will be linked to the value of the “UI 3 Configuration” object. When the “UI 3 Configuration” object value is 0, 3 or
4, the value will be set to “Deactivated.”
Object Name
Object Type
and Instance
Inactive_Text Active_Text Default value
Room Temp Override BV 8 Normal Override Normal
Room Humidity Override BV 11 Normal Override Normal
Dehumidification Lockout BV 13 Disabled Enabled Enabled
AUX Command BV 14 Off On Off
Dehumidification Status BI 23 Off On Off
Aux Status BI 25 Off On Off
BI 1 Status BI 29 Deactivated Activated Deactivated
BI 2 Status BI 30 Deactivated Activated Deactivated
UI 3 Status(*) BI 31 Deactivated Activated Deactivated
Local Motion BI 32 No Motion Motion No Motion
Window Alarm BI 35 Off On Off
Filter Alarm BI 36 Off On Off
Service Alarm BI 37 Off On Off
Menu Scroll BV 49 No Scroll Scroll Active Scroll Active
Auto Mode Enable BV 50 Disabled Enabled Enabled
Temperature Scale BV 51 °C °F °F
Setpoint Type BV 60 Permanent Temporary Permanent
Setpoint Function BV 61 Dual Setpoints Attached
Setpoints
Dual Setpoints
Reheat Time Base BV 64 15 minutes 10 seconds 15 minutes
Auto Fan BV 66 Auto Speed Auto Speed / Auto
Demand
Auto Speed
RH Display BV 70 Disabled Enabled Disabled
Control Type BV 75 On/Off Floating On/Off
Direct/ Reverse Acting BV 78 Direct Acting Reverse Acting Direst Acting