Honeywell TB7200 Thermostat User Manual


 
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
21 63-4524—01
Property Value Range Restrictions
Table 8. Property value range restrictions.
Object name
Object Type
and instance
Minimum range
value
Maximum
range value
Default value
Room Temperature AV 7 -39.9°F (-40°C) 121.9°F (50°C) N/A
Outdoor Temperature AV 9 -39°F (-40°C) 121.9°F (50°C) N/A
Room Humidity AV 10 5% 90% N/A
Supply Temperature AI 12 -39.9°F (-40°C) 121.9°F (50°C) N/A
PI Heating demand AV 21 0% 100% 0%
PI Cooling demand AV 22 0% 100% 0%
Occupied Heat Setpoint AV 39 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Occupied Cool Setpoint AV 40 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
Stand-by Heat Setpoint AV 41 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Stand-by Cool Setpoint AV 42 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
Unoccupied Heat Setpoint AV 43 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
Unoccupied Cool Setpoint AV 44 54°F (12°C) 100°F (37.5°C) 80°F (26.5°C)
Password Value AV 56 0 1000 0
Heating Setpoint Limit AV 58 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 59 54°F (12°C) 100°F (37.5°C) 54°F (12°C)
Deadband AV 63 2°F (1°C) 5°F (2.5°C) 2°F (1°C)
Stand-by Time AV 67 0.5 Hours 24.0 Hours 0.5 Hours
Unoccupied Time AV 68 0.0 Hours 24.0 Hours 0.0 Hours
RH Setpoint AV 45 30% 100% 50%
Dehumidification Hysterisys AV 46 2% 20% 5%
Dehumidification MAX cooling AV 47 20% 100% 100%