Honeywell T8611G Thermostat User Manual


 
T8611G CHRONOTHERM
®
IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
5 69-1406—1
Adaptive
Intelligent
Recovery™
control.
13 0 Adaptive Intelligent
Recovery™
control is activated
(system starts
early so setpoint is
reached by start of
program period).
1 Conventional recovery
(system starts recovery at
programmed time).
Degree
temperature
display
14 1 Temperature is
displayed in °C
Temperature is displayed in
°C
Not Used. 15
Clock format. 16 0 12-hour clock
format.
1 24-hour clock format.
Not Used. 17 thru 23
Outdoor
temperature
display (models
with OT
terminals).
24 0 No outdoor
temperature is
displayed.
1 Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Temperature Sensor to
operate.
Not Used. 25 thru 28
O/B terminal
energized in
heating or
cooling.
29 0 O/B terminal
energized for
reversing valve in
cooling.
1 O/B terminal energized for
reversing valve in heating
Deadband 30 3 Heating and
cooling setpoints
can be set no
closer than 3°F
(1.5°C).
4 thru 10 Heating and cooling
setpoints can be set no
closer than the chosen
value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Not Used. 31 and 32
Minimum off
time for the
compressor.
33 5 5 minute minimum
off time for the
compressor.
0 thru 4 Minimum number of minutes
(0 thru 5) the compressor
will be off between calls for
the compressor.
Temperature
range stops in
heating.
34 90 Highest heating
setpoint setting.
40 thru 89 Temperature range (1°F
increments) of heating
setpoint settings.
Temperature
range stops in
cooling.
35 45 Lowest cooling
setpoint setting.
46 thru 99 Temperature range (1°F
increments) of cooling
setpoint settings
Not Used. 36
Table 3. Thermostat Installer Setup Options. (Continued)
Select
Installer Setup
Number (Press
Time key to
change)
Factory Setting
Other Choices
(Press or key to change)
Actual
SettingDisplay Description Display Description