Honeywell T8600D Thermostat User Manual


 
T8600D, T8601D AND T8602D CHRONOTHERM
®
IV DELUXE PROGRAMMABLE THERMOSTATS
68-0164—1
8
Table 6. Thermostat Installer Setup Options.
(continued)
Installer Setup
Number (Press
Time key to
Factory-Setting
Other Choices
(Press or key to change)
Actual
Select
change)
Display Description Display Description
Setting
Not used 1
Fan operation
a
20Conventional
applications where
equipment controls fan
operation in heat mode
1 Heat pump or electric heat
applications where thermostat
controls fan operation in heat
mode
Not used 3
Heating cycle
rate
466—6 cph used for
conventional heat
1, 3 or 9 1—1 cph used for radiant floor
heat, gravity system
3—3 cph used for hot water
systems or high efficiency
furnaces
9—9 cph used for electric heat
systems
Not used 5 thru 11
System setting
adjustment
12 1 Manual changeover 0 or 2 0—Auto changeover
2—Fixed auto changeover
Adaptive
Intelligent
Recovery™
control
13 0 Adaptive Intelligent
Recovery™ control is
activated (system
starts early so setpoint
is reached by start of
program period)
1 Conventional recovery (system
starts recovery at programmed
time)
Degree
temperature
display
14 0 Temperature is
displayed in °F
1 Temperature is displayed in °C
Not used 15
Clock format 16 0 12-hour clock format 1 24-hour clock format
Not used 17 and 18
Extended fan
operation in
heating
a
19 0 No extended fan
operation after the call
for heat ends
1 Fan operation is extended 90
seconds after the call for heat
ends.
Extended fan
operation in
cooling
20 0 No extended fan
operation after the call
for cool ends
1 Fan operation is extended 90
seconds after the call for cool
ends.
Not used 21 thru 23
Outdoor
temperature
display (select
models)
24 0 No outdoor
temperature is
displayed
1 Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor Sensor
to operate
Not used 25 thru 29
Deadband 30 3 Heating and cooling
setpoints can be set
no closer than 3°F
(1.5°C)
4 thru 10 Heating and cooling setpoints
can be set no closer than the
chosen value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
a
Number 2 must be set to 1 to extend fan operation.