Honeywell T7200E Thermostat User Manual


 
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355412
Extended fan
operation in heat
a
(T7300F only).
19 0 No extended fan operation after
call for heat ends.
1 Fan operation extended 90 sec after call for
heat ends.
Extended fan
operation in
cooling
(T7300F only).
20 0 No extended fan operation after
the call for cooling ends.
1 Fan operation is extended 90 seconds after
the call for cooling ends.
Fan key
adjustment
(models with Fan
key).
21 0 Fan setting key operational. 1 Fan setting key is Auto only.
Remote sensing. 22 0 Remote sensing not activated. 1 Remote sensing activated.
Temperature
averaging network
b
(T7300F only).
23 0 Temperature averaging disabled. 1 Temperature averaging between local
sensor and remote sensor(s) activated.
Not used. 24
Keypad lockout
level (keypad
lockout enabled/
disabled by DIP
switch 1 on
thermostat back).
(T7300F only)
25 0 No lockout. 1, 2 or 3 1: Lockout all thermostat keys except
system and fan settings, temporary
setpoint, clock and day adjustments,
increase and decrease .
2: Lockout all keys except Set Current Day/
Time, increase and decrease .
3: Lockout all keys except Temporary
Occupied and Set Current Day/Time (for
clock, day adjustment).
Duration of
temporary
override.
26 3 3: Three hour override. 1, 8 or
12
1: One hour override.
8: Eight hour override.
12: Twelve hour override.
Not used. 27 through 29
Deadband
(T7300F only).
30 2 Heating and cooling setpoints can
be set no closer than 2°F (1.1°C).
3 - 10 Heating and cooling setpoints can be set no
closer than the chosen value.
Interstage control
point (T7300F,
Q7300C,D only).
31 0 Disabled. 1 - 12 Temperature must change more than
chosen value before system calls for next
stage. (Example: heat setpoint: 68°F (20°C),
interstage setting: 2°F (1.1°C), temperature
is 65.5°F (18.5°C). Second stage turns on,
brings temperature to 66°F (19°C) and turns
off. Heat pump continues to run until setpoint
is reached.
Minimum on- time
(T7300F).
32 2 2-minute minimum on- time for
heating and cooling.
0 or 1 No minimum on-time or 1-minute minimum
on-time for heating and cooling.
Minimum
compressor off-
time.
33 4 4-minute minimum compressor
off-time.
0, 1, 2, 3
or 5
Minimum number of minutes (0 through 5)
compressor is off between compressor calls.
Temperature heat
range stops
(T7300F).
34 90 Highest heat setpoint. 40 to 89 Heat setpoint temperature range (1°F
increments).
Temperature
cooling range
stops (T7300F).
35 45 Lowest cooling setpoint. 46 to 99 Temperature range (1°F increments) for
cooling setpoint.
Not used. 36
Table 7. Thermostat Installer Setup Options. (Continued)
Select
Installer Setup
Number
(Press Unoccupied
Temp to change)
Factory Setting
Other Choices
(Press
or
to change)
Actual
SettingDisplay Description Display Description
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.