Honeywell MS-9200UDLSE Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 139
Ademco Contact ID & SIA Formats
The information shown in Table 3.3 is automatically programmed for the Central Station phone
number Event Codes when the Ademco Contact ID or SIA Format is selected. Enter 0s for an
Event Code Setting to disable the report. Disabled reports will not get called to the Central
Station. The programmer may enable the Event Types in programming as described on the
previous page.
Table 3.3 Event Codes
Event Description Ademco Contact ID SIA
Active Active Restoral
PULL STATION 115 FA FH
MON-USER-DEF-1 115 FA FH
WATERFLOW 113 SA SH
MON-USER-DEF-2 113 SA SH
SMOKE (PHOTO) 111 FA FH
DET-USER-DEF-1 111 FA FH
SMOKE (ION) 111 FA FH
DET-USER-DEF-2 111 FA FH
HEAT DETECT 114 KA KH
DET-USER-DEF-3 114 KA KH
SMOKE DUCT-P 116 FA FH
DET-USER-DEF-4 116 FA FH
PHOTO W/HEAT 111 FA FH
DET-USER-DEF-5 111 FA FH
DUCT SUPERVISORY 200 FS FV
DET-USER-DEF-6 200 FS FV
PHOTO SUPERV 200 FS FV
DET-USER-DEF-7 200 FS FV
PHOTO ADAPT 111 FA FH
DET-USER-DEF-8 111 FA FH
PHOTO BEAM 111 FA FH
DET-USER-DEF-9 111 FA FH
not used 000 00 00
not used 000 00 00
not used 000 00 00
not used 000 00 00
not used 000 00 00
not used 000 00 00
not used 000 00 00
not used 000 00 00
not used 000 00 00
not used 000 00 00
MONITOR 110 FA FH
MON-USER-DEF-3 110 FA FH
not used 000 00 00
not used 000 00 00
SMOKE CONVEN 111 FA FH
MON-USER-DEF-5 111 FA FH
HEAT CONVENTIONAL 114 KA KH
MON-USER-DEF-6 114 KA KH
MEDIC ALERT 100 MA MH
MON-USER-DEF-7 100 MA MH
HAZARD ALERT 150 PA PH
MON-USER-DEF-8 150 PA PH
TORNADO ALRT 150 PA PH
MON-USER-DEF-9 150 PA PH
MON-PHONE 000 00 00
MON-USER-DEF-10 000 00 00
TAMPER 144 TA TH
MON-USER-DEF-11 144 TA TH
MON SUPERVISORY 200 FS FV
MON-USER-DEF-12 200 FS FV
MON SUPERV AUTO 200 FS FV