Honeywell MS-9200UDLSE Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 115
3.6.9 Option Modules
Options available for the MS-9200UDLS include ACS Series, Graphic and LCD
annunciators, printer connection for acquiring hardcopy printouts of panel data and PC
(Personal Computer) connection for uploading and downloading panel data.
Pressing 3 while viewing Programming Screen #3 will display the following screen:
Note that PR4800 in the display indicates that a supervised printer, configured for 4800
baud, has been previously programmed into the system.
3.6.9.1 Annunciators
Pressing 1 while viewing the Options Screen will cause the control panel to display
the following screens:
A Terminal Mode annunciator, ACS Mode annunciator or ANN-BUS annunciator/
module can be installed in the MS-9200UDLS system. Do not use a mix of ACS
annunciators and ANN annunciators since they use different communication
protocols. ACS or ANN annunciators use the same TB9 terminal block connection.
To install any of these devices, press the number corresponding to the desired
device shown in the Annunciator Screen.
3.6.9.1.1 Term Options
While viewing the Annunciators screen, each press of the 1 key for Term Enabled,
will cause the display to toggle between Term Enabled No and Term Enabled Yes.
Notes:
1. *The LCD-80F is a Terminal Mode annunciator. To enable the MS-9200UDLS
for LCD-80F operation, press 1 for Term Enabled Yes.
2. The Terminal Mode annunciator (LCD-80F) and the Printer/PC use the same
TB8 terminal block on the MS-9200UDLS main circuit board. Only one device
can be connected at one time, therefore, enabling an annunciator in the Term
Option will disable any Printer/PC communications.
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
OPTION MODULES
1=ANNUNCIATORS
2=ONBOARD DACT
3=PRINTER/PC PR4800
Options Screen
ANNUNCIATORS
1=TERM ENABLED NO
2=ACS OPTIONS
3=ANN-BUS OPTIONS