Honeywell MS-9200UDLSE Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 133
3.6.9.2.4.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to
answering an incoming call from a service terminal. The factory default is 0 which
means the control panel will not answer an incoming call. This entry may be
programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2.
The following screen will be displayed:
A flashing cursor will appear in the lower left corner of the display. Enter the two-
digit ring count which can be a value between 00 and 25. After the second digit is
entered, the display will return to the Service Terminal screen.
3.6.9.2.5 Central Station
Central Station programming configures the control panel DACT for contacting the
central station. Pressing 2 while viewing On Board DACT Screen #2 will cause the
following screens to be displayed:
3.6.9.2.5.1 Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press 1 while
viewing Central Station Screen #1 so the display reads Reporting Enabled. Each
press of the 1 key will toggle the display between Reporting Disabled and
Reporting Enabled.
SERVICE TERMINAL
1=RING COUNT
Service Terminal Screen #2
RING COUNT
RANGE 0-25 RANGE
Ring Count Screen
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
CENTRAL STATION
1=REPORTING DISABLED
2=REPORT BACKUP
3=CALL LIMIT
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2