Honeywell F90B Air Cleaner User Manual


 
F90A,B SELF-CONTAINED COMMERCIAL ELECTRONIC AIR CLEANER
68-0103-6 Revised 11-07
5
STAGE
DANCE FLOOR
T
A
B
L
E
S
BAR
LOW SMOKING LEVEL AT 
STAGE AND DANCE FLOOR. 
USE ONE F90.
HEAVY SMOKING LEVEL AT 
TABLES AND BAR.
USE THREE F90s.
M1528A
F90
F90
F90
F90
F90
F90
F90
F90
F90
F90
Fig. 4. F90 mounting considerations.
M923
Fig. 5. F90 Coanda air flow pattern.
Outdoor Air
ASHRAE Standard 62-89 specifies that every commercial
space be provided with fifteen cfm per occupant of outdoor
air to replenish oxygen and dilute CO2. If other internal
sources of gaseous contamination are present, additional
outside air is needed to dilute the contamination.
EXAMPLE: An office requires 20 cfm per person because
the standard estimates some smoking, some
copy machine operation, etc. The standard
assumes outdoor air will be cleaned to less
than 75 micrograms per cubic meter prior to
introduction into the space. ASHRAE Standard
62-89 states that supplemental air cleaning to
control smoke or additional outside air must
be provided as required.
Example 1. Sizing by Air Changes per Hour and Room Volume
An office measures 40 x 45 feet (12 x 14 meters) with a 15 foot (4.5 meter) ceiling. How many F90As should be installed?
Solution:
1. Find the room volume: 40 x 45 x 15 feet = 27,000 cubic feet, (12 x 14 x 4.5 meters = 756 cubic meters).
2. Assuming seven air changes per hour, with 27,000 cubic feet (756 cubic meters) volume, the graph below indicates three
F90As are required.
3. Clean outdoor air is also required to replenish oxygen and dilute gaseous contaminants. 20 cfm per person is required for
offices.
1
2
3
4
5
6
7
8
9
10
F90As REQUIRED
25
20
15
10
5
0
10,000
[283]
20,000
[567]
30,000
[850]
40,000
[1133]
50,000
[1416]
60,000
[1700]
70,000
[1983]
ROOM VOLUME IN CUBIC FEET AND [CUBIC METERS]
CAFETERIAS
LUNCHEONETTES
BARS
RESTAURANTS
STORES
OFFICES
BOWLING
CENTERS
PLACES OF
ASSEMBLY
M1524
AIR 
CHANGES 
PER HOUR