F58F COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER
68-0141—4
5
The air cleaner can be mounted in any position except with
the access door facing down.
Multiple electronic air cleaner installations are needed for
many commercial systems. Air cleaners can be mounted
back-to-back.
Carefully plan the number of air cleaners and positions before
beginning installation. To visualize the plan of installation,
temporarily arrange the desired number of air cleaners on the
floor. Consider the air cleaners total dimensions, clearance
and accessibility before selecting a location.
ALLOW 13 IN. [330 MM] MINIMUM FOR CELL AND SCREEN REMOVAL.
1
M5769
1 1
Back-to-Back Mounting
When mounting two cabinets back-to-back, allow at least
13 in. (330 mm) on each side (total of 26 in. [660 mm]) to
remove cells and protective screens for cleaning. See Fig. 3.
Allow 1/4 to 3/8 in. (6.4 to 9.6 mm) between adjoining back
ends of the cabinet for protruding tray tabs. Tray tabs extend
1/8 in. (3.2 mm) and must not be bent.
Fig. 3. Typical multiple installation of F58F Electronic Air Cleaners.