Honeywell F58F Air Cleaner User Manual


 
F58F COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER
68-0141—4
2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
Model:
F58F Commercial Electronic Air Cleaner: Includes cabinet,
access door, solid state power supply, two electronic cells and
two prefilters.
Electrical Ratings:
Voltage and Frequency: 120V, 60 Hz. Two-cell 120V, 60 Hz
models can be converted in the field to 240V, 60 Hz or
220/240V, 50 Hz with the 203365A kit.
Power Consumption: 36W maximum
Current Draw: 0.4A at 120V, 60 Hz and 0.2A at 240V,
60 Hz or 220/240V, 50 Hz.
Ionizer Voltage: 8150 Vdc.
Collector Voltage: 4075 Vdc.
Capacity, Efficiency, Pressure Drop:
See Fig. 1.
Temperature Ratings:
Operating Ambient: 40°F to 125°F (4°C to 52°C).
Temperature of Airflow Through Cells: 40°F to 125°F
(4°C to 52°C).
Maximum Cell Washing Temperature: 220°F (140°C).
Storage and Shipping Ambient: Minus 40°F to plus 140°F
(minus 40°C to plus 60°C).
Mounting:
Mounts in the return air duct of a forced air heating, cooling,
or ventilating system. Should be mounted upstream from the
atomizing humidifier. See Planning the Installation section.
Weight:
Electronic Cell (each): 9 3/16 lb (4.2 kg).
Shipping Weight: 42 lb (19.1 kg).
Installed Weight (cells included): 37 lb (16.8 kg).
Dimensions:
See Fig. 2.
Approvals:
Underwriters Laboratories Inc. Listed: File No. E30954.
Canadian Standards Association Certified: File No.
LR95329-1.
Accessories:
203365A Conversion Kit for changing 120V, 60 Hz power
supply to 240V, 60 Hz or 220/240, 50 Hz.
W8600F Air Cleaner Monitor.
Repair Parts:
See Replacement Parts/Exploded View section.