Honeywell 8000 Thermostat User Manual


 
9 62-0266—01
0690 Temperature
Control Cool
2 1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if
system has cool
stages.
Only integral gains
affected. Affects
control operation in
all control regimes
(not just recovery
or setpoint
change).
More Aggressive
stops signal prior to
reaching the
setpoint. (For use
with oversized
equipment.)
0695 Recovery
Cool Ramp
Rate
3 0-20° F/hour
(-18- -7° C)
Only shown if
system has cool
stages.
0 disables ramped
recovery (step
setpoint change at
period start time).
0700 Temperature
Display
Offset
0 -3 (-1.5)— -3° F (-1.5° C)
-2 (-1.0)— -2° F (-1.0° C)
-1 (-0.5)— -1° F (-0.5° C)
0 (0.0)—0° F (0.0° C)
1 (0.5)—1° F (0.5° C)
2 (1.0)—2° F (1.0° C)
3 (1.5)—3° F (1.5° C)
This offset applies
to both the control
temperature and to
the display
temperature for
indoor sensor (and
remote indoor
sensor).
0710 Restore
Factory
Defaults
0 0—No
1—Yes
Resets all ISU
parameters to
default values and
resets the schedule
to default. Retains
only calendar
settings and time.
Table 1. Installer Setup (Continued).
Installer
Setup
Number
Installer
Setup
Name
Default
Setting All Settings Notes